|
LOCATION
Self-contained
air conditioners can be located anywhere in lockers, under bunks
or settees and in furniture to avoid taking up additional floor
space. In some cases the air conditioner may be put into the bilge
area. However it is important to ensure that water cannot splash
onto the air conditioner when the boat is underway. The air conditioner
itself is more commonly installed at floor level allowing for high
level air discharge via the ducts as described above. Chiller systems
generally have the chiller unit installed in a separate hold or
engine compartment with only the air handlers located in the cabins.
Air distribution is the same as with self-contained air conditioners.
 |
 |
GRILLES
AND LOUVRES
For the cold air to exit, air outlet grilles have to be installed.
These are connected to the flexible ducting and should generally
be placed as high as possible. If it is not possible to install
them at window ledge height it is recommended that they be installed
at an angle so that the air is directed towards the centre of the
deckhead. Return air grilles should be installed as close to the
floor as possible to allow the air to be filtered and enter the
airconditioner without restriction. Grille sizes and duct sizes
are listed in separate data sheets.
 |
RETURN AIR APERTURE SYSTEMS
In some cases it is necessary to return the air from two or
even three cabins. The air is guided through so called return air
apertures and ducted to the airconditioner from which it is distributed
back into the cabins. For these applications HFL offer components
which make the installation easy and efficient. The return air apertures
also ensure that the bilge smell cannot enter the cooling air circuit.
ENCLOSURES
Sometimes it is necessary to mount the airconditioner in a
glass fibre enclosure, particularly when the unit is mounted below
the floor and is subject to bilge water splashing. Such GRP enclosures
also help to reduce noise and lend themselves to be used within
the return air aperture system. Noise can be reduced by using soft
hush covers with a lead lining. These are placed over the compressor
and can be extremely effective.
CONTROLS
A variety of controls are on offer, from simple 3-knob controls
consisting of system switch, speed controller and thermostat to
sophisticated environmental control units, i.e. programmers which
allow high and low temperatures to be set and can include many other
features. The HFL ECU pack offers a total programme selection of
some 64 different options including such features as electrical
diagnosis for voltage and current, 6-step variable speed control
and many others.
RELAY
BOX
Single
seawater pump with relay box or several pumps ? For multi air conditioner
installations owners can choose between a large single seawater
pump with a relay box to control the signal from each control panel,
or separate seawater pumps for each airconditioner. The latter requires
increased plumbing. Since the seawater pump is the part most vulnerable
to corrosion, electrolysis and other damage, it is generally thought
to be more satisfactory to use one seawater pump per airconditioner
in an installation with up to four airconditioners. In an installation
with a greater number of units an arrangement with single pumps
and relay boxes is generally preferred. With such installations
owners should be prepared to keep a spare seawater pump and relay
box on board.
HOW
MANY BTU'S OR Kcal - How much airconditioning?
Firstly decide on the areas to be airconditioned, then calculate
their volume. To obtain the cooling capacity required multiply the
cabin volume by specific multipliers as follows:-
Volume in m³
m³
x 612 = BTU for area above deck
m³ x 504 = BTU for area below deck
4
BTU = 1 Kcal
Volume in cu.ft
cu.
ft X 17 = BTU for area above deck
cu. ft x 14 = BTU for area below deck
For vessels operating in areas with ambient temperatures above 30ºC
add up to a further 20%. In areas with high sea water temperature,
i.e. above 25ºC, add a further 20% since the airconditioner will
also have to remove large quantities of radiated surface heat entering
the boat via the hull.
BTU's (British Thermal Units) represent the amount of energy required
in order to heat or cool a given area. This energy potential can
also be expressed in Kcal (kilo calories). Approximately four BTU's
equal one Kcal. The table shows the relationship between BTU's and
cabin area in SqFt. It also includes the effects of the location
of the cabin board.
Below deck areas are generally well insulated and have limited window
area which effect heat/cold losses greatly. Resulting from this
chart and assuming that the equipment is installed properly using
the correctly sited seawater pump, Room temperatures for cool of
between 16-22ºC should be achieved. Calculate 3.5 Gallons of seawater
per minute per self-contained unit. This applies for airconditioning
units from 6-16000 BTU's
ELECTRICAL DEMAND
The electrical consumption depends on the size of the airconditioner.
The larger the compressor, the larger the amperage required. The
voltage may be either 110 volt for a 60Hz system or 220 volt for
a 50Hz system. In most cases the power is single phase. The operating
current is generally indicated on the manufacturers plate. This
however, does not state the starting current. Hermetically-sealed
AC compresssors, have a high starting current requirement although
this is generally reduced via capacitors etc. to a manageable level
of approx 3-5 times the running current. Larger ratios between starting
and running current should not be considered for pleasure craft
airconditioner applications. Such heavy starting currents would
create overload problems for either the shore supply or smaller
generators. The starting current generally applies only for a shore
period, say 300-400 milliseconds but as soon as the compressor is
running the current drops back to normal level. It is important
that the correct circuit breaker is selected and when doing so the
running current for the seawater pump also has to be taken into
account since the compressor and seawater pump often run simultaneously.
|